General specifications |
Signal type |
Analog input |
Supply |
Connection |
Power Rail or terminals 11+, 12- |
Rated voltage |
20 ... 35 V DC |
Ripple |
within the supply tolerance |
Rated current |
< 20 mA |
Input |
Connection side |
field side |
Connection |
terminals 4+, 5- |
Input resistance |
min. 10 MΩ |
Transmission range |
0 ... 12 V |
Offset voltage/current |
< 2 mV / < 7 nA |
Output |
Connection side |
control side |
Connection |
terminals 7-, 8+ |
Voltage |
0 ... 12 V |
Output resistance |
max. 20 Ω |
Transfer characteristics |
Cut-off frequency |
1.2 kHz (-3 dB) |
Deviation |
|
|
After calibration |
± 5 mV at 20 °C (68 °F) |
|
Influence of ambient temperature |
≤ 0.005 % of range per K |
Rise time |
≤ 0.4 ms |
Galvanic isolation |
Output/power supply |
functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements |
LED |
Labeling |
space for labeling at the front |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility |
NE 21 |
Degree of protection |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection |
IP20 |
Connection |
screw terminals |
Mass |
approx. 100 g |
Dimensions |
20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate |
BAS 01 ATEX 7262 |
|
Marking |
II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2] |
|
Voltage |
18 V |
|
Current |
4.2 mA |
|
Power |
19 mW |
Supply |
|
|
Maximum safe voltage |
250 V (Attention! The rated voltage is lower.) |
Output |
|
|
Maximum safe voltage |
250 V (Attention! The rated voltage is lower.) |
Certificate |
baseEFA 10 ATEX 0079X |
|
Marking |
II 3G Ex nA II T4 Gc [device in zone 2] |
Galvanic isolation |
|
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
|
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
Directive 2014/34/EU |
EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval |
|
|
Control drawing |
116-0129 |
UL approval |
|
|
Control drawing |
116-0173 (cULus) |
CSA approval |
|
|
Control drawing |
116-0132 |
IECEx approval |
|
|
IECEx certificate |
IECEx BAS 10.0040X |
|
IECEx marking |
Ex nA IIC T4 Gc |
General information |
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Accessories |
Optional accessories |
- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03) |